GASMONITOR SYSTEM GASMASTER DETECTOR-FLAMGARD
GAS DETECTOR - Tx GARD CSM 500G (Portable) CSM200 (Portable)
GASMAN II Series CUSTODIAN

¥°. Specifications
Model/ Assembly
IS
D
HS
Plus
Operating temperature range
-20 to 40¡É
-20 to 55¡É
-20 to 80¡É
-10 to 55¡É
Operating humidity range
0¡­99% RH
non-ondensing
0¡­99% RH
non-condensing
0¡­99% RH
non-condensing
0¡­99% RH
non-condensing
Dimensions
160¡¿122¡¿85
190¡¿129¡¿85
190¡¿129¡¿85
180¡¿115¡¿115
Weight
0.65Kg
4Kg
4Kg
2.2Kg
Display
-
-
-
LCD 3 digit backlit display, LED status indicator, Magnetically actuated alibration button
Repeatability
¡¾2% FSD
¡¾2% FSD
¡¾2% FSD
¡¾2% FSD
Zero drift
¡¾2%FSD,6months
¡¾2%FSD,6months
¡¾2%FSD, 6months
¡¾2%FSD, 6months
Response time
T50<5s, T90<10s
T50<5s, T90<10s
T50<5s, T90<10s
T50<5s, T90<10s
Zones
0, 1 or 2
1 or 2
1 or 2
1 or 2
Electrical output
2 wire, loop, powered, 4-20mA
2 wire, loop, powered, 4-20mA
3 wire,4-20mA (sink/source) 2mA=inhibit (selectable as 4mA) 4-20mA=Normal 25mA=over range (clamped)
3 wire 4-20mA (sink/source) 0mA=Fault 2mA=inhibit (4mA option) 4-20mA=Normal 24mA=over range (clamped)
Relay output
-
-
-
Separate alarm and fault relays, rated 1A 30V dc (NO or NC selectable)
Operating voltage (typical)
10-30V dc
10-30V dc
10-30V dc
10-30V dc
Power requirements (typical)
24mA maximum

 

24mA maximum

 

25mA maximum
180mA @ 10V dc 120mA @ 24V dc